PP & PPR - Technical Specifications
Switch-mode Rectifiers for Plating > PP & PPR > Technical Specifications
Previous | Next
ELECTRICAL SPECIFICATIONS
 
Q100 model
Q300 model
Q500 model
Output
Max current per tower PP
550/1650A
1700/5100A
8000/24000A
PPR
250(750)A
1100(3300)A
5000(15000)A
Voltage PP
5-450VDC
PPR
5-50VDC
Max. pulsed current
Up to 3 times the max DC current value depending on the pattern required
Operation Mode
Current control or Voltage Control (limited)
Control accuracy
1/1000 of max current or voltage
Current regulation range
2 - 100% of max current (With CTRD02)
Voltage regulation range
5 - 100% of max voltage (With CTRD02)
Current ripple (RMS)
< 2.0% of rated output current in current operation mode (< 1.0% on Request)
Efficiency
89% (typ.) @ rated load / 92% (for >= 160VDC) @ rated load
Min. Pulse duration
Slow: 3ms | Fast: 1ms
Secondary withstand voltage
50VAC 50Hz 1min. between Secondary to earth
Pole to be connected to ground
Positive
Main
Supply
Line voltage
3 x 230VAC ± 10%, 3 x 400VAC ± 10%, 3 x 440VAC ± 10%,
3 x 480VAC ± 10% or 3 x 550VAC ± 10% or 3 x 575VAC ± 10%
Frequency
50 - 60Hz
Neutral
NOT USED
Power factor
> 95% @ rated load
Primary current in max DC
Max 20A
Max 55A
Max 230A per tower
Earth leakage current
See EMC filter input specifications
 



GENERAL SPECIFICATIONS
 
Q100 model
Q300 model
Q500 model
Technology
Switching mode PWM, Full Bridge IGBT inverter
Cooling Systems
Air
Water
Operation
Conditions
Location
Indoor use only
Ambient temperature
0 - 40°C (up to 50°C with 15% derating -air cooled- / 10% derating -water cooled-)
Relative humidity
15 - 85% not condensing
Filter obstruction - air cooled
15% max
Water input temp. - water cooled
19 - 22°C (rectifier rev. A1-A49) | 19 - 28°C (rectifier rev. A60 or above)
Altitude
<= 2000m
Degree of Protection
Air cooled
IP31
IP21 (on request NEMA12)
IP32
Water cooled
IP43
-
IP42 (on request IP65)
Enclosuer color
RAL 3004
RAL 5010
RAL 3004
Conformity of EU Directives
2006/95/EC - Low Voltage Directive
2004/108/EC - Electromagnetic Compatibility
 



PROTECTION
Surge
According to Directive EN 61000-4-5
2kV between each input phase and PE. 1kV across each input phase combination.
Phase Loss
Type Hardware Software
Programmed limit Half cycle Adjustable via configuration parameter
 
Output Short Circuit
Type Software
Programmed limit 25% of Iout_max
Detection Time 1ms
Thermal Protection
With PTC on each module
 



SERIAL INTERFACE
Communication Ports
RS232
RS485
Communication Protocols
CRS-ASCII Included RS232 point-to-point and RS485 network
Modbus-RTU Included RS232 point-to-point and RS485 network
Profibus-DP Optional with additional board Profibus-DP network
DeviceNet Optional with additional board CAN bus network
Modbus/TCP Optional with additional board Ethernet
Profinet Optional with additional board Ethernet
EthernetIP Optional with additional board Ethernet
 



 
FULL LOAD HARMONICS DISTORTION
Harmonic
Freq. (Hz)
Absorbed Current Distortions
 
3
150
-
 
5
250
< 22.5%
 
7
350
< 12.5%
 
9
450
-
 
11
550
< 11.0%
 
13
650
< 7.6%
 
17
850
< 8.0%
 
19
950
< 4.8%
 
THD
MAX 30%
 
 




Last update: May/17/2016