ELECTRICAL SPECIFICATIONS |
|
|
Q100 model |
Q300 model |
Q500 model |
Output |
Power |
DC |
Up to 8kW |
Up to 32kW (Max 3 power modules) |
Up to 110kW per tower (Max 9 power modules) |
DCR |
Up to 4kW |
Up to 20kW (Max 1 reverse module) |
Up to 100kW per tower (Max 3 reverse modules) |
Voltage |
DC |
5 - 450VDC standard |
DCR |
5 - 50VDC standard |
Operation Mode |
Current Control or Voltage Control |
Control accuracy |
1/1000 of max current or voltage |
Precision |
99% on entire range |
Current regulation range |
5 - 100% of max current (On Request 2% Available) |
Voltage regulation range |
10 - 100% of max voltage (On Request 5% Available) No voltage regulation without load |
Current ripple (RMS) |
< 2.0% of rated output current in current operation mode (< 1.0% on Request) |
Efficiency |
87% (typ.) @ rated load / 92% (for >= 160VDC) @ rated load |
Regulation speed |
10 - 90% in 250ms with 100ms reverse dead time |
Secondary withstand voltage |
50VAC 50Hz 1min. between Secondary to Earth |
Pole to be connected to ground |
Positive |
Main Supply |
Line voltage |
3 x 230VAC ± 10%, 3 x 400VAC ± 10%, 3 x 440VAC ± 10%,
3 x 480VAC ± 10% or 3 x 550VAC ± 10% or 3 x 600VAC ± 10% |
Frequency |
50 - 60Hz |
Neutral |
NOT USED |
Power factor |
> 93% @ rated load |
Primary current |
Max 20A |
Max 55A |
Max 230A per tower |
Earth leakage current |
See EMC filter input specifications |
|